Configuration
April 2021
2.7.2
Verifying configuration with AMS Device Manager
Right select on the device and select Configuration Properties from the menu. Navigate
the tabs to review the transmitter configuration data.
2.7.3
Verifying configuration with LOI
Press any configuration button to activate the LOI. Select VIEW CONFIG to review the
below parameters. Use the configuration buttons to navigate through the menu. The
parameters to be reviewed prior to installation include:
•
Tag
•
Units
•
Transfer function
•
Alarm and saturation levels
•
Primary variable
•
Range values
•
Damping
2.7.4
Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary and
2.8
Basic setup of the transmitter
This section goes through the necessary steps for basic setup of a pressure transmitter.
2.8.1
Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
20
quaternary variables.
Rosemount 2088, 2090P, and 2090F Pressure Transmitter Reference Manual
3, 2, 1
Reference Manual
00809-0100-4108