Related Parameters and Monitors
■
Added Parameters
Parameter
Operator Display
(Hex.)
L8-05
Inp Ph Loss Det
(04B1)
L8-65
PF Min Current
(067B)
L8-70
Pf dv/dt Level
(066F)
L8-79
dv/dt TuneFactor
(067E)
L8-81
OutPhLs PMInjCur
(067F)
■
Added Monitors
Monitor
Operator Display
(Hex.)
U4-62
PF dVdt ErrCount
(085B)
U4-64
PF Max dVdtValue
(0859)
U4-65
PF dVdtValue
(085A)
11
Direct Landing 2
◆
Overview
When you activate Direct Landing, the drive decelerates within a fixed distance to the floor level while it does a
positioning operation. You can define the distance to the floor, and also the frequency reference when Direct
Landing is activated.
YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
Description
Input Phase Loss Detection Method
Enables or disables the input phase loss detection.
0 : Disabled
Lift controller decides the direction with S1/S2
2 : Enabled during operation
6 : Standard + dv/dt
dv/dt @Start and Standard detection during RUN
PF Detection Minimum Current Level
PF detection minimum current level; % of drive rated current. Used for both,
standard method and dv/dt method (only during run, not evaluated for dv/dt
detection method at start)
PF Detection Level
Sets the DC bus dv/dt threshold value.
dV/dt tuning factor
Factor applied to the dv/dt value(s) which have been determined during tuning.
The result is stored to the parameter(s) if tuning was completed successfully.
Output Phase Loss PM Injection Current
Injection current for PM motor to detect output phase loss before the brake
opens.
Description
PF detection error counter
Shows a percentage value less than 100%. If the value is different to zero,
there have been dv/dt threshold exceeding events. Upon reaching 100%, PF
fault is triggered and the counter is reset to 0%.
Note:
Only applies for dv/dt Input Phase Loss detection method.
PF detection maximum dV/dt value
Shows the maximum dv/dt value from the previous (or the current, while
running) travel. The value is reset at start and only updated while the drive is
running. When powering on (no previous travel), zero is shown.
The value is shown as absolute maximum dv/dt value (the internal value is
negative). The unit of this value is V/s but not shown in the operator.
Note:
Only applies for dv/dt Input Phase Loss detection method.
PF detection actual dV/dt value
Shows the current dv/dt value with sign. The value unit is V/s but not shown in
the operator.
Note:
Only applies for dv/dt Input Phase Loss detection method.
11 Direct Landing 2
Value Range
Default Value
0, 2, 6
2
0.0 ... 100.0 %
10.0 %
0 ... 10,000 V/s
2,500 V/s
100 ... 200 %
105 %
0 ... 50.0 %
5 %
Analog Output
Scaling (H4-xx
Unit
selection)
-
ms
-
ms
-
-
EN