Advertisement

U =
Δ / Y 400 ΔV
P =
6.7 kW
S5 240, F/h 50 % ED
IEC34 - 1
Parameter No.
E1-04
E1-05
E1-06
E1-09
E2-01
E2-02
E2-03
E2-11
S1-07
S1-10
S6-02
S6-03
S6-04
*1
According to the (Example) Motor Nameplate.
4.
Enter the Auto-Tuning menu.
5.
Set parameter T1-01 = 2 [Stationary Auto-Tuning for Line-to-Line Resistance].
6.
Enter the nameplate data in the Auto-Tuning menu.
• T2-02 = Motor Power (kW)
• T2-04 = Motor Current (Amps)
7.
After entering the data listed on the motor nameplate, press the UP-button until the following message is
displayed: "0.00 Hz/0.00 A Tuning Ready? Press RUN key".
YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum
9 Replacement Instructions for Smart Controller Drives
Table 9.3 Motor Nameplate (Example)
f =
33 Hz
I =
13.5 A
Protection degree =
IP21
Table 9.4 Recommended Parameters (Example)
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Minimum Output Frequency
Motor Rated Current
Motor Rated Slip
Motor No Load Current
Motor Rated Power
Brake Close Delay Time
Run Command Delay Time
Starting Current Error (SE2) Detection Delay
Time
SE2 Detect Current Level
Output Current Error (SE3) Detection Delay
Time
Figure 9.4 Tuning ready?
cos φ 0,85
RPM =
950 min
-1
Starting Torque =
TA/TN 2.75
Inertia =
I mot 0,32 kgm
2
Insulation =
KI F
Setting Value
*1
33 Hz
400 V
*1
*1
33 Hz
*1
0.1 Hz
*1
13.5 A
1.30 Hz
*1
*1
6 A
*1
6.7 kW
0.3 s
0.4 s
500 ms
35 %
500 ms
77
EN

Advertisement