Error
Code
Description
(hex)
0E
Attribute not settable
13
Not enough data
14
Attribute not supported Attempted to execute a service not defined for the attribute.
15
Too much data
16
Object does not exist
1F
Vendor-specific error
20
Invalid parameter
Note: Refer to the MEMOBUS/Modbus Data Table in Appendix C of the V1000 Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
EtherNet/IP Option Error Codes
EtherNet/IP Option Fault Monitors U6-98 and U6-99
The EtherNet/IP Option can declare error/warning conditions via drive monitor parameters on the drive digital operator as
shown in
Table
17.
Fault Condition
No Fault
Force Fault
Network Link Down
Connection Time-out
Duplicate IP Address
Default MAC Address
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present EtherNet/IP Option SI-EN3/V status. U6-99 is cleared upon a network-issued fault reset and
upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
YASKAWA ELECTRIC SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Attempted to change a read-only attribute.
The data size is incorrect.
The data size is incorrect.
An unsupported object was specified.
Attempted to change a drive constant that cannot be changed
while the drive is running.
Attempted to change a drive constant to a value outside the
setting range.
Attempted to change to a data value outside the setting range.
Table 17 EtherNet/IP Option Fault Monitor Descriptions
Status Value
Fault Declared
(U6-98/U6-99)
n/a
EF0
BUS ERROR
1100
BUS ERROR
1101
BUS ERROR
1102
None
1103
Cause
0
No faults
3
Network sent a message to force this node to the fault state
No network link to option board
The node timer (Requested Packet Interval) timed out
This node and at least one other node have the same IP Address
Factory default MAC Address programmed into EtherNet/IP Option.
Return for reprogramming.
13 Troubleshooting
Possible Solution
Correct the service code or attribute setting.
Correct the data size.
Correct the service code or attribute setting.
Correct the data size.
Correct the class or instance setting.
Stop the drive.
Specify a value within the setting range.
Specify a data value within the setting range.