12 Vendor-Specific (Yaskawa) Class Objects
Yaskawa Monitor/Control Object 125 (Class 0x7D)
Services Supported
Service Code No. (hex)
This is a dynamic explicit Class Object. With this Class object any parameter with a MEMOBUS/Modbus address less
than 0x0100 can be accessed. This class is similar to the Drive Parameters Object Class 100, except that since the most
significant byte of MEMOBUS/Modbus address is always zero, the instance in this class remains at "1".
Given a typical MEMOBUS/Modbus Address 0f 0x00YY
The EtherNet/IP Instance value is equal to 0x01
The EtherNet/IP Attribute value is equal to YY
As an example, to access Drive Status (MEMOBUS/Modbus Address = 0x002C)
Class Object is 125 (0x7D) (Always for this Class Object)
Instance = 0x01
Attribute = 0x2C
Attributes Supported
Instance ID
Attribute
0
1
1
1
1
2
..
..
1
255
Note: Attempting to set a read-only parameter results in a EtherNet/IP error code of 0x0E, Attribute Not Settable.
Note: Attempting to access an invalid parameter results in a EtherNet/IP error code of 0x09, Invalid Attribute Value.
56
0E
10
MEMOBUS/Modbus
Address
-
0x0001
0x0002
..
0x00FF
Description
Object Software Revision
Drive Command Bits
Frequency Instruction
..
Unused
YASKAWA ELECTRIC SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Service Name
Get Attribute Single
Set Attribute Single
Get
Set
O
-
O
O
O
O
O
O
O
O
Size
Word
Word
Word
Word
Word