9 Output Assemblies (Drive Consumes)
Extended Speed and Torque Control Output - 23 (0x17)
Output Instance
Byte
23
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
Speed Reference
Torque Reference
28
Bit 7
Bit 6
0
NetRef
1
2
3
4
5
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
(0 to 1 transition: Fault Reset)
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference / 2
Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096 / 2
Unit depends on o1-03.
Not supported on V1000
Bit 5
Bit 4
NetCtrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Torque Reference (Low Byte), not supported on V1000
Torque Reference (High Byte), not supported on V1000
Description
SS
(SS: Speed scale)
2
= 1024 = 0x0400
YASKAWA ELECTRIC SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Bit 3
Bit 2
Bit 1
Fault
Run
Reset
Rev
Bit 0
Run
Fwd