YASKAWA SI-EN3/V Technical Manual page 30

Ac drive-v1000 option ethernet/ip
Hide thumbs Also See for SI-EN3/V:
Table of Contents

Advertisement

9 Output Assemblies (Drive Consumes)
Speed/Torque Control Output (Vendor Specific YE Assy) - 101 (0x65)
Output
Byte
Instance
Multi-Function
0
Multi-Function
1
Photo Coupler
2
101
3
4
5
6
7
Output Instance
Run Fwd
Run Rev
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output
Multi-Function Photo Coupler 1
30
Bit 7
Bit 6
Multi-Function
Multi-Function
Input 8
Input 7
Multi-Function
Multi-Function
Photo Coupler
Digital Output
2
1
Torque Reference (Low Byte), not supported on V1000
Torque Reference (High Byte), not supported on V1000
Torque Compensation (Low Byte), not supported on V1000
Torque Compensation (High Byte), not supported on V1000
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
Not supported on V1000
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
0: No Fault Reset
1: Fault Reset
Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Bit 5
Bit 4
Multi-Function
Multi-Function
Input 6
Input 5
Speed Reference (Low Byte)
Speed Reference (High Byte)
Byte
YASKAWA ELECTRIC SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Bit 3
Bit 2
Multi-Function
Input 4
Input 3
Bit 1
Bit 0
Run
Run
Rev
Fwd
Fault
External
Reset
Fault

Advertisement