2.19 @AA(Data)

Description:
The command is used to set the digital output channels of the
module.
Syntax:
@AA(Data)[CHKSUM](CR)
@
Delimiter character
AA
Address of the module in hexadecimal format (00
to FF)
(Data)
The data to be written to the digital output
channels. A single-digit hexadecimal value. Bit 0
of the value corresponds to the DO channel. A bit
value of 1 denotes that the digital output channel
is on, and a bit value of 0 denotes that the digital
output channel is off.
Response:
Valid Command:
Invalid Command:
Ignored Command:
>
Delimiter for a valid command
?
Delimiter for an invalid command
!
Delimiter for an ignored command:
If a Host WatchDog Timeout occurs, the module
will reset to safe mode and the DO output
>[CHKSUM](CR)
?AA[CHKSUM](CR)
![CHKSUM](CR)
67/93 I-87211W User Manual V2.5, Oct. 2010