2.1 % AANNTTCCFF

Description:
This command is used to set the configuration of a module.
Syntax:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
Address of the module to be configured in
hexadecimal format (00 to FF)
NN
New address of the module in hexadecimal format
(00 to FF)
TT
Type Code (Refer to Section 1.9 configuration table)
The type Code of the GPS-721 is fixed as 40
CC
Refer to the module section 1.9 configuration
table. The BaudRate is not set when the modules
is not in Init mode
FF
0
Response:
Valid Command: !AA[CHKSUM](CR)
Invalid Command: ?AA[CHKSUM](CR)
!
Delimiter for a valid command
?
Delimiter for an invalid command
AA
Address of the module in hexadecimal format
(00 to FF)