Aa0A(Data) - ICP DAS USA I-87211W User Manual

Table of Contents

Advertisement

2.6 #AA0A(Data)

Description:
This command is used to set the digital output value of the
module.
Syntax:
#AA0A(Data)[CHKSUM](CR)
#
Delimiter character
AA
Address of the module in hexadecimal format (00
to FF)
0A
Command to set the digital output value for the
lower eight channels
(Data)
A two-digit hexadecimal value Bit 0 corresponds
to DO0 and Bit 1 corresponds to DO1
A bit value 1 of denotes that the digital output
channel is on and a bit value of 0 denotes that the
digital output channel is off
Response:
Valid Command:
Invalid Command:
Ignored Command:
>
Delimiter for a valid command
?
Delimiter for an invalid command
!
Delimiter for an ignored command:
If a Host WatchDog Timeout occurs, the module
will reset to safe mode and the DO output
>[CHKSUM](CR)
?AA[CHKSUM](CR)
![CHKSUM](CR)
43/93 I-87211W User Manual V2.5, Oct. 2010
I-87211W User Manual