Indigo NXT QuietQube/CVD: Sequence of Operation
Auto Shut-Off – Condensing Unit
** This is to reduce short cycling for pump down cycles / short cycling. **
1
2
Equalize
Purge
45 Sec
5 Sec
1.
With the liquid line solenoid valve closed the refrigeration system
pumps down.
2.
The head pressure falls below the fan cycling control cut-out and the
condenser fan motor stops.
3.
The suction pressure drops below the low pressure switch cut-out
a) R-404a = 12 psig cut out.
b) R-410a = 20 psig (30 psig differential).
4.
The contactor opens and the compressor shuts-off.
5.
When the LPC opens there will be a 5 minute delay before the ice
machine and CVD Condensing unit can re-start due to the Delay on
Break-Lock out solid state timer located in the Condensing Unit.
3
Pre-Chill
Start
30 Sec.
Ice Thickness
5 Sec
(thereafter)
4
5
Harvest
Freeze
Purge
45 Sec
Probe
7
Auto Shut Off
(10 Minute Delay)
6
Bin Switch Open
for more than
Harvest
30 seconds
Bin Switch