Indigo NXT QuietQube/CVD: Sequence of Operation
Water Level Probe Operation (WLP)
• During freeze cycle the water level
will drop away from the "High"
Probe.
• Water valve will energize again until
the "High" probe is satisfied and stay
energized for an additional 6 seconds.
• Single Evaporator: Maximum water
fill time is 6 minutes per fill X2 fills
during freeze.
• Dual Evaporator: Maximum water
fill time is 8 minutes per fill X2 fills
during freeze.
NOTE: at the end of Freeze the water level should
not be touching the WLP.