6 WEIGHING SETTING AND OPERATIONS
6
WEIGHING SETTING AND
OPERATIONS
6-1.
Comparison mode
(setting mode 1-4 weighing function 1)
On the F701-P, three weighing methods can be selected by comparison mode.
Select from three comparison modes.
6-2.

Near zero comparison

Chapter
6
This function is to detect that the weight value is near zero.
Near zero can be set as desired. The comparison condition depends on the near zero comparison
mode.
- Near zero (setting mode 0-3)
Input range/0 - 99999
- Near zero comparison mode (weighing function 1 in setting mode 1-4)
Select the condition for near zero comparison.
38
38
Weighing function 1
Weighing function 1
Comparison mode
0: Upper/Lower limit comparison mode
1: Over/Under comparison mode
2: Discharging control mode
Near zero comparison mode
0: Near zero signal ON when
gross weight ≦ near zero setting value
1: Near zero signal ON when
net weight ≦ near zero setting value
2: Near zero signal ON when
|gross weight| ≦ near zero setting value
3: Near zero signal ON when
|net weight| ≦ near zero setting value
4: Comparison OFF
* When the near zero signal is on, "
" lights.