18. Technical Specifications

Zones
Maximum number of detectors per zone
*
Including 20 (or 32 SensoMAG) automatic detectors and/ or manual call points.
Thresholds for zone conditions
• 0 - 2 mA
• 2 - 10 mA
• 10 - 110 mA
• 110 mA - Short circuit
Power supply
Main Power supply
Standby Power supply, accumulator
Maximum charging current for the battery
Battery high resistance Ri
Consumption
Maximum current available for system
devices (with fully charged battery)
Minimum current for standby power supply -
mains failure
Maximum current for standby power supply
Outputs
Sounder Circuit 1
Sounder Circuit 2
Fault Relay, volt free changeover contacts**
Fire Relay, volt free changeover contacts**
**
Note: These functions may not be used to provide any "Options with requirements" as specified
in EN 54-2.
Auxiliary output
Cabling
Environment
Working temperature
Storage temperature
Humidity
Compatible modules
MR8 - 8 Relay Module
ML - Log Memory Module
Attention: It is possible to connect only one module to the MAG8 fire panel at the same
time!
Fire Control Panel MAG8 - Installation and Operation Manual
8 fixed zones
Up to 32 devices*
Open circuit fault condition.
Normal condition.
Fire Alarm condition.
Short circuit condition.
230V AC ±10%; 0.315A fuse
1 x 12V/7Ah (7.2Ah); 4.5A fuse
type Sealed Lead-Acid, 150x95x65mm
0.3 A
< 0.45Ω
0.7 A
0.125 A
4,5 A
24V / 0.5A; 0.5A fuse (PTC)
24V / 0.5A; 0.5A fuse (PTC)
3A @ 24V DC
3A @ 24V DC
24V DC, 0.3A fuse (PTC)
Maximum 2.5mm diameter
-5 to 40°C
-20 to 60°C
0 to 95%
17