How To Save The Log File; How To Update The Firmware (Mc-3000S) - Furuno FAR-3320-NXT Instruction Manual

Hide thumbs Also See for FAR-3320-NXT:
Table of Contents

Advertisement

2. SETTING FOR SENSOR ADAPTER
How to restore the default Equipment ID
When you can not define the Equipment ID of the sensor adapter, restore the default
and set the Equipment ID again.
1. Turn on the No. 8 segment of the DIP switch S10 on the board in the MC-3000S,
then turn on the sensor adapter.
The Equipment ID of the sensor adapter turns to default "MCV016", and the IP ad-
dress is set to "172.31.17.108".
2. See section 2.1 "How to Set the Equipment ID" to set the Equipment ID of the sen-
sor adapter.
3. Turn off the No. 8 segment of the DIP switch S10 on the board in the MC-3000S.
2.2

How to Save the Log File

The log file of the sensor adapter can be saved to a medium (PC, USB memory, etc.).
The log file is used to check the status of the sensor adapter.
1. Connect the PC to the sensor adapter with the LAN cable.
2. Activate the web browser and enter the following address in the address bar.
"http://172.31.xx.xxx/cgi-bin/logall.cgi"
"172.31.xx.xxx" is the IP address of the sensor adapter where to save the log file.
3. After entering the address, the window to save the log file appears. Save the log
file to the PC.
2.3

How to Update the Firmware (MC-3000S)

This section shows you how to update the firmware program of the sensor adapter
MC-3000S.
Preparation
• PC that has a LAN port
Windows
dress and subnet mask of the PC as shown below.
IP address: 172.31.16.200
Subnet mask: 255.255.0.0
• LAN cable
• Binary file for update
2450080-xxxxxxxx_mc_cs_boot.bin
2450081-xxxxxxxx_mc_cs_mainpg.bin
2450082-xxxxxxxx_mc_cs_maint.bin
2450084-xxxxxxxx_mc_io_mainpg.bin
(xxxxxxxx: program version)
2-2
®
®
XP or Windows
7 can be used. Disable the firewall and set the IP ad-
Boot program
Main program
Maintenance program
Main program (analog, digital input,
and digital output board)