Fig. 148 Selection Of The Oversampling Variable With The Target Browser; Fig. 149 Appending The Variable "Aui_Samples" Below "Axis" Within The Scope Project Of The Solution Explorer - Beckhoff EL3783 Documentation

Power monitoring oversampling terminal for 690 v
Table of Contents

Advertisement

The selection of PDO "U1 Samples" of the EL3773 for "MAIN.aUI_Samples" based by the last preceding
paragraph Step 2a as illustrated above have to be done in the same way for "Var 1" accordingly.
Step 4: Selection of the PLC array variable for the Y-axis of the scope
Now the configuration will be activated (
visible for the target browser of the scope for being selected.
Thereby the drop down menu will be opened by right clicking on "Axis" (A) for selection of the scope features
(B):
Fig. 148: Selection of the oversampling variable with the target browser
By addressing the corresponding system that represents the PLC containing the array variable ("Any PC
(CX2040)" in this case) navigation up to the variable "aUI_Samples" (C) have to be done.
Fig. 149: Appending the variable "aUI_Samples" below "axis" within the scope project of the solution explorer
Variable don't appears into the target browser
If „ROUTES" don't offer a possibility for selection of the provided variables, the corresponding port
should be declared for the target browser:
Using "Add symbol" displays the variable "aUI_Samples" below "axis" within the scope project of the solution
explorer directly.
EL3783
) and logged in the PLC (
Version: 1.1
Commissioning
), so the array variable will be
117