Mounting and wiring
Wiring
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
Fig. 25: Mounting a cable on a terminal connection
Up to eight connections enable the connection of solid or finely stranded cables to the Bus Terminals. The
terminals are implemented in spring force technology. Connect the cables as follows:
1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening
above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire securely and per-
manently.
Terminal housing
Wire size width
Wire stripping length
High Density Terminals ELx8xx, KLx8xx (HD)
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the contact point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Terminal housing
Wire size width (conductors with a wire end sleeve)
Wire size width (single core wires)
Wire size width (fine-wire conductors)
Wire size width (ultrasonically "bonded" conductors)
Wire stripping length
34
ELxxxx, KLxxxx
2
0.08 ... 2,5 mm
8 ... 9 mm
Version: 1.1
ESxxxx, KSxxxx
2
0.08 ... 2.5 mm
9 ... 10 mm
High Density Housing
2
0.14 ... 0.75 mm
2
0.08 ... 1.5 mm
2
0.25 ... 1.5 mm
2
only 1.5 mm
(see notice [} 33]!)
8 ... 9 mm