Selecting local and remote
1. To select local control, press the LOC / REM key.
The local control location is indicated by the
letter L.
2. To select remote control, press the LOC / REM
key. The remote control location is indicated
by a blank (see arrow).
3. The keypad can also be used as a remote control
place. In this case, the parameters 11.01, 11.02,
12.03 or 12.06 must be set to KEYPAD. In this
setup the remote control location is indicated by
the letter R. The START/STOP commands and the
reference value can be set from the CDP control
panel.
Locking local or remote control mode
Accidental switching from remote control to local
control can be prevented with the lock function of
parameter 16.04.
The parameter 16.04 LOCAL LOCK locks or unlocks
the LOC / REM key of the CDP control panel and
determines the control place where the lock
function is activated (CDP control panel
or remote control location).
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
Local control location
1
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
Remote control location
1 R
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
Remote control location
Enable lock function
The lock function is disabled if the parameter 16.04
is set to 1 (= OPEN). Switching from local to remote
and vice versa is possible.
Disable lock function
The lock function is enabled if the parameter 16.04
is set to 2 (= LOCKED). In this case, local cannot be
selected on the CDP control panel. However, the
CDP control panel or the DriveWindow PC will
remain in local mode (if they were already in local
mode when the parameter was set to locked) until
the CDP control panel is switched to remote.
The letter L remains on the display until the LOC /
REM key is pressed.
Setting the direction of rotation
The direction of rotation is selected using the
forward (I) or reverse (0) key of the CDP control
panel. Both keys can be used if the CDP control
panel is in local mode. The function is released
with parameter 11.03 DIRECTION (REQUEST).
1 L ->
StateINU
MOTOR SP
POWER
1 L <-
StateINU
MOTOR SP
POWER
The arrow on the display indicates the direction:
• When the motor is running, the arrow indicates
the actual direction of rotation
• When the motor is not running, the arrow
indicates the preselected direction of rotation
When the direction of rotation is changed while the
motor is running, the speed will automatically ramp
to zero and the motor will accelerate in the
opposite direction to the preset speed. The
direction of the arrow on the display changes
to the new direction when the motor has
reached zero speed.
600.0 rpm
ReadyRun
600.00 rpm
75.0 kW
Forward rotation
600.0 rpm
ReadyRun
600.00 rpm
75.0 kW
Reverse rotation