ABB ACS2000 User Manual page 58

Medium voltage drives
Hide thumbs Also See for ACS2000:
Table of Contents

Advertisement

58
A C S 2 0 0 0 , 4 K V U S E R M A N U A L
DANGER
WARNING
Drive installation
65
Anchor bolt
CAUTION
General notes on installation
66
Direct-to-floor
NOTICE
base mounting
NOTICE: When installing the drive, ensure that no
67
dirt enters. Always close the doors when work is
Frame 1 Fan outlet box
discontinued and completely cover openings.
Metallic dust, in particular, may cause
malfunction when the drive is powered
up and may cause damage.
The cabinet roof is not designed as a mounting
base for foreign devices, cable ducts, etc.
Therefore, do not install any foreign device
on the top of the drive.
Dimensions and clearances
See Layout drawing in Appendix D - Mechanical
drawings, located on the CD, for specific
information on the dimensions of the
drive and clearances to be observed.
• Cabinet dimensions
• Clearances to be observed
• Mounting hole sizes
Base mounting
ABB recommends that the drive be attached to the
floor during installation.
There is one acceptable means to attach the
cabinet to the floor: direct-to-floor mounting.
Floor mounting hardware is not supplied by ABB.
65
Anchor bolts as illustrated or hardware as specified
in the chart are recommended (see Figure 65).
Size
M12
1/2 inch
Grade
Dry torque value
8.8
40 Nm
5
45 ft-lbs
Direct-to-floor mounting
The cabinet provides a slot in each corner of the
base to attach the drive to the floor.
Install the mounting hardware through slots
outside the cabinet (see Figure 66).
1
1
Slot for screw
2
Cabinet frame
66
Fan outlet box installation - Frame 1 (if required)
1
Fan outlet box
67
• Dimensions: (L x W x H) 1150 x 840 x 180 mm [45 x
33 x 7 in]
• Weight: Approximately 37 kg [80 lbs]
• Tools : Torx screwdriver or 10 mm hex wrench to
install the hexagon fastening screws
2