T r o U b l e S h o oT i n G a n d m a i n T e n a n c e
Fieldbus communication adapters
110
Fieldbus communication
adapter
1
The drive can be equipped with one of the
following fieldbus adapters.
Table 27: Fieldbus adapters
Fieldbus
Modbus
Ethernet
Profibus DP/FMS
Anybus DeviceNet Module
Anybus EtherNet IP Module
Anybus ControlNet Module
See Appendix E - Wiring diagrams, located on the
CD, to identify the adapter type installed in your
drive.
See Appendix B - Fieldbus adapter manuals, located
on the CD, for detailed information.
Maintenance
Overview of maintenance and service tasks
• Visual checks on the drive
See section Visual checks on the drive
• Checking wire and cable connections
See section Checking wire and cable connections
• Checking and replacing filter mats
See section Checking and replacing filter mats
• Replacing a phase module
See section Replacing a phase module
See Service and maintenance manual for
information on maintenance and service work other
than described in this manual.
Fieldbus communication adapter
Option code
+FAMM0
+FAME0
+FAMP0
+FAMAD
+FAMAE
+FAMAC
Safety
DANGER
DANGER: Hazardous voltages!
WARNING
Follow proper lock out and tag out safety
procedures. Failure to do so may result in death or
CAUTION
serious injury.
1
NOTICE
Before starting with maintenance, make sure that:
• Personal protective equipment is provided and
used when required
• Everyone involved is informed
• The main power supply is switched off, locked out
and tagged out
• Rack out the MV switchgear, lock it in open
position, and tag it
• Safety ground connections are in place.
• The auxiliary power supply is switched off, locked
out and tagged out
• The voltage is 0 V at the supply terminals when
checked using a multimeter
• The MV switchgear control power supply is
switched off and locked out
• If an optional 120 V control power or space heater
is installed, these supplies are switched off and
locked out
Before energizing the drive again, make sure that:
• All foreign objects are removed from the drive
• All internal and external covers are securely
fastened and all doors are closed, locked and
/ or bolted
DANGER
DANGER: Hazardous voltages!
WARNING
When maintenance on the drive is carried out that
includes the removal of phase modules, the
CAUTION
DANGER
connection of grounding equipment at the
appropriate locations is a must. The grounding
WARNING
NOTICE
equipment ensures that hazardous voltages
cannot be fed into the drive from the main
CAUTION
power supply or from the motor.
NOTICE
NOTICE: When working on the drive, ensure that
foreign matter cannot enter the cabinet. Close the
doors and cover openings completely when work is
discontinued. Any foreign matter which
accidentally dropped into the cabinet must be
retrieved. Metallic dust, in particular, could cause
malfunction and damage when the drive is
energized.
101