T r o U b l e S h o oT i n G a n d m a i n T e n a n c e
Checking and replacement indications
Filter mats should be checked regularly. The
intervals in which the mats are checked depend
on the cleanliness of the cooling air.
The filter mats are monitored by a pressure sensor.
When the mats are clogging and the pressure drop
reaches the specified final pressure loss, the
message Conv1CoolAirFilter comes up on the CDP
control panel and the alarm/fault pilot light on the
control compartment door illuminates.
Replacement
Although checking and removing of a filter mat can
be performed during operation of the drive, it is
easier to do when the drive is shut down.
When replacing a filter mat while the drive is
running, work carefully to prevent foreign matter
from entering the drive. Also, pay attention that
dust accumulated on the filter mat is not sucked
into the cabinet.
Note: ABB recommends removing the old filter mat
by rolling it down from the top to the bottom.
Filter mat replacement procedure
Filters can be replaced while the drive is running,
as they are accessible from the outside. Caution
DANGER
should be made not to shake filter in front of
drive to avoid sucking contaminants into the drive.
WARNING
CAUTION: While filter grills are finger safe, be
CAUTION
aware that components on the inside may be
electrically live and action should be taken to
NOTICE
avoid contact with tools or fingers.
1. Remove the ventilation grill of the corresponding
section.
The ventilation grills are secured to the cabinet by a
channel.
Lift the grill to the slot position and remove.
2. Visually check the filter mat. If the filter mat
needs replacement, go on to Step 3. If the mat is
clean, replace the grill as in Step 5.
3. Remove the filter mat Remove the filter mat,
being careful not to disturb accumulated dust, by
rolling the mat down from the top to the bottom.
4. Install a new filter mat. Use only replacement
filter mats of the same filter class, thickness, and
size as the original filter mat:
• Filter class: G3 (EN779)
• Thickness: approximately 10 mm [0.4 in]
• ABB supplies replacement filter mats as
specified in Table 28
Table 28: Filter mat identification
INU and AFE
ABB
replacement
Filter mat
part number
Frame 1
2UEA001026
Frame 2
2UEA001704
Frame 3
2UEA002487
Input Filter Unit
ABB
replacement
Filter mat
part number
Frame 1
2UEA001042
Frame 2
2UEA001694
Frame 3
2UEA001694
Place the new filter mat against the opening. Tuck
the edges into the metal frame.
Ventilation grill
105
Width
Height
Qty
mm [in]
mm [in]
2
445 [17.5]
740 [29.0]
2
830 [32.7]
795 [31.3]
4
550 [21.7]
795 [31.3]
Width
Height
Qty
mm [in]
mm [in]
1
600 [23.5]
1120 [44.0]
1
646 [25.4]
610 [24.0]
1
646 [25.4]
610 [24.0]