m e c h a n i c a l i n S Ta l l aT i o n
74
Frame 1 Redundant
fan installation
75
Frame 1 Redundant
fan power supply
connections
76
Frame 1 Inlet ring
installation
77
1
Redundant fan housing
Frame 1 Fan installation
2
Sealing gasket
3
Predrilled holes
4
Drive's redundant fan wiring
5
Terminal block
74
4. Fasten the fan unit using the supplied screws.
The predrilled holes (see Figure 74 - Frame 1)
are fitted with press nuts on the underside.
5. Make the terminal block to drive wiring
connections.
The front wall of the fan box may be removed for
easier access to the wiring.
A. Remove the upper IFU (Input Filter Unit) panel to
access the drive wiring for the redundant fan.
B. Carefully feed the wires from the drive up into
the fan unit housing and route to the terminal
block.
C. Make the wiring connections.
2
1
Terminal block X22
2
Wire numbers
3
External fan power supply
75
6. Bolt the fan inlet ring to the top of the drive.
1
3
2
3
5
4
1
Fan inlet ring
76
7. Install the fan in the fan box.
1
Fan
2
Fan wires
3
Terminal block
77
8. Route the fan wires (see Figure 77 - Frame 1) and
1
connect to the terminal block.
9. Check that the flapper is moving freely.
10. Reattach the front panel and the cover of the
fan unit.
61
1
2
1
3