A C S 2 0 0 0 , 4 K V U S E R M A N U A L
Table 13: Standard digital inputs signal allocation
Terminal
X11-1
X11-2
X11-3
X11-4
X11-5
X11-6
X11-7
X11-8
X11-9
X11-10
X12-1
X12-2
X12-3
X12-4
X12-5
X12-6
X12-7
X12-8
X12-9
X12-10
X13-1
X13-2
X13-3
X13-4
X13-5
X13-6
X13-7
X13-8
X13-9
X13-10
* Not configurable. When the integral input contactor disconnect is installed, these signals are prewired.
IOEC2 (A1541) analog inputs
Table 15: Standard analog input signal allocation
Analog input resolution 10 bit
Voltage mode
Signal range 0...10 V
Load impedance 250 kΩ
Channel
DI01
DI02
DI03
DI04
DI05
DI06
DI07
DI08
DI09
DI10
DI11
DI12
DI13
DI14
+24 V
+0 V
Current mode
Signal range 0...20mA
Load impedance 105 Ω
Default setting
Par. Group
External start/stop request
Common
72.06 to 72.09
Forward/reverse
Common
72.10 to 72.11
Freely programmable
Common
-
Ramp 1/2
Common
72.41 to 72.42
Ext1/Ext2
Common
30 to 31
Constant speed select
Common
24 to 25
External on request (start DC
link charge)
Common
72.02 to 73.03
Process stop (stops drive)
Common
72.43 to 72.44
MV switchgear open
Common
*
MV switchgear closed
Common
*
MV switchgear available (not
tripped)
Common
*
Remote reset
Common
72.33 to 72.34
External OFF request
Common
72.04 to 72.05
Disable local operation
Common
72.35 to 72.36
24 V control logic
Common
-
Remote speed supply output specifications
• Output voltage 10 V
• Available output current 5 mA
Terminal
Channel
Default setting
X31-1
+10 V
X32-1
0 V
Internal supply voltage -
X31-2
AI1+
Reference value 1
X32-2
AI1-
(speed reference)
Reference value 2
X31-3
AI2+
(speed or torque
X32-3
AI2-
reference)
X31-4
AI3+
Motor winding V
X32-4
AI3-
temperature
X31-5
AI4+
Motor winding W
X32-5
AI4-
temperature
Par. Group