ABB ACS2000 User Manual page 50

Medium voltage drives
Hide thumbs Also See for ACS2000:
Table of Contents

Advertisement

50
A C S 2 0 0 0 , 4 K V U S E R M A N U A L
IOEC4 (A1621) digital outputs
Table 17: Optional digital output signal allocation
DC voltage
24 VDC
48 VDC
120 VDC
AC voltage
24 VAC
48 VAC
120 VAC
230 VAC
Terminal
X21-1
X21-2
X21-3
X22-1
X22-2
X22-3
X23-1
X23-2
X23-3
X24-1
X24-2
X24-3
X25-1 *
X25-2 *
X25-3 *
X26-1 *
X26-2 *
X26-3 *
Current Switching Continuous
8 A
6A
1 A
6A
0.4 A
6A
Current Switching Continuous
8 A
6A
8 A
6A
8 A
6A
8 A
6A
Channel
Default setting
DO01
Freely programmable
DO02
Freely programmable
Freely programmable
(for motor space heater
then motor heater OFF
DO03
command)
Freely programmable
(for motor cooling fan
then motor cooling fan
DO04
ON command)
DO05
Freely programmable
DO06
Freely programmable
IOEC4 (A1621) digital inputs
Table 18: Optional digital inputs signal allocation
Current
Signal level direct
Typ 24 VDC max 100 VDC
Signal level alternating
Typ 24 VAC max 230 VAC
Input
8...25 mA
Inrush 24 V
0mA
Inrush 120 V
Typ 65mA max 100mA
Terminal
Channel
Default setting
X11-1
Freely programmable
X11-2
DI01
Common
X11-3
Freely programmable
X11-4
DI02
Common
X11-5
Freely programmable
X11-6
DI03
Common
X11-7
Freely programmable
X11-8
DI04
Common
X11-9
Freely programmable
X11-10
DI05
Common
X12-1
Freely programmable
X12-2
DI06
Common
X12-3
Freely programmable
X12-4
DI07
Common
X12-5
Freely programmable
X12-6
DI08
Common
X12-7
Freely programmable
X12-8
DI09
Common
X12-9
Motor protection monitoring
X12-10
DI10
Common
Motor vibration 2/bearing 2 (alarm
X13-1
trip)
X13-2
DI11
Common
Motor vibration 1/bearing 1 (alarm
X13-3
trip)
X13-4
DI12
Common
Ext mot trip (ovrtmp/ovrspd/space
X13-5
htr/fan)
X13-6
DI13
Common
X13-7
External motor alarm
X13-8
DI14
Common
X13-9
24 V control logic
+24 V
X13-10
+0 V
Common

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents