LED
Parameter
display
name
F29
[Torque boost
in reverse
direction]
F30
[V/F pattern]
F31
[User V/F
3)
frequency 1]
F32
[User V/F
voltage 1]
F33
[User V/F
frequency 2]
F34
[User V/F
voltage 2]
F35
[User V/F
frequency 3]
F36
[User V/F
voltage 3]
F37
[User V/F
frequency 4]
F38
[User V/F
voltage 4]
F39
[Output voltage
adjustment]
F40
[Energy-saving
level]
F50
[Electronic
thermal
select]
2) Only displayed when F24 (Freq High/Low limit select) is set to 1.
3): Set F30 to 2 (User V/F) to display this parameter.
Min/Max
range
This parameter sets the amount of torque
boost applied to a motor during reverse run.
It is set as a percent of Max output voltage
0/2
0
{Linear}
1
{Square}
2
{User V/F}
This parameter is active when F30 – [V/F
0/400 [Hz]
pattern] is set to 2 {User V/F}.
It cannot be set above F21 – [Max
0/100 [%]
frequency].
The value of voltage is set in percent of
0/400 [Hz]
H70 – [Motor rated voltage].
The values of the lower-numbered
0/100 [%]
parameters cannot be set above those of
higher-numbered.
0/400 [Hz]
0/100 [%]
0/400 [Hz]
0/100 [%]
40/110
This parameter adjusts the amount of
[%]
output voltage.
The set value is the percentage of input
voltage.
0/30 [%]
This parameter decreases output voltage
according to load status.
0/1
This parameter is activated when the
motor is overheated (time-inverse).
Description
7-5
7. Function list
Function group 1
Factory
Adjustable
defaults
during run
5
X
0
X
15.0
X
25
X
30.0
X
50
X
45.0
X
75
X
60.0
X
100
X
100
X
0
0
0
0
SV-iC5
Page
9-17
9-15
9-15
9-16
9-16
9-16
10-12
12-1