9. Basic functions
Frequency setting via Potentiometer on the keypad + Current Analog input (0-20mA)
Group
LED Display
Drive
0.0
group
Frq
Select Frq – [Frequency Mode] to 5 {Potentiometer on the keypad and Current Analog input (0-20mA)}.
Override function is provided via Main speed and Auxiliary speed adjustment.
Related code: I 1 - I 5, I 11- I 15
When main speed is set via potentiometer and Auxiliary speed via 0-20mA analog input, the override
function is set as below.
Group
I/O group
After the above setting is made, if 5V is set via potentiometer and 10mA is applied via I terminal, 32.5Hz is output
Frequency setting via 0-10V + 0-20mA input
Group
LED Display
Drive
0.0
group
Frq
Set Frq – [Frequency Mode] to 6 {V1 + I terminal input}.
Related code : I 6 - I 10, I 11 - I 15
Refer to the Frequency setting via Potentiometer on the keypad + Current Analog input (0-20mA) for the
setting.
Parameter Name
[Frequency Command]
[Frequency Mode]
Code
I 2
[V0 input minimum voltage]
I 3
[Frequency corresponding to I 2]
I 4
[V0 input max voltage]
I 5
[Frequency corresponding to I 4]
I 12
[I input minimum current]
I 13
[Frequency corresponding to I 12]
I 14
[I input max current]
I 15
[Frequency corresponding to I 14]
Parameter Name
[Frequency Command]
[Frequency Mode]
Set
Min/Max
Value
Range
-
5
Parameter Name
Set
Min/Max
Value
Range
-
6
9-4
Factory
Defaults
-
-
0/8
0
Set
Units
value
0
0
Hz
10
60.0
Hz
4
mA
0
Hz
20
mA
5.0
Hz
Factory
Defaults
-
-
0/8
0
SV-iC5
Unit
Hz
V
V
Unit
Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents