More precise time unit can be set corresponding to load characteristics as shown below.
Code
Parameter Name
H71
[Accel/Decel Time setting
unit]
Accel/Decel time based on Run frequency
Group
LED display
Drive
ACC
group
dEC
Function
H70
group 2
Accel/Decel time is set at the ACC/dEC.
If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a target freq from run
freq (Currently operating freq.).
When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,
(A zone: run freq 10 Hz applied first, B zone: Operating via 10 Hz, different run freq is not issued
C: 30Hz Run freq (in this case, Target freq) issued while 10 Hz run freq is applied. But the preset accel time
5 sec is maintained. )
Setting range
0.01~600.00
0.1~6000.0
1~60000
Parameter name
[Accel time]
[Decel time]
[Frequency reference for
Accel/Decel]
Freq.
command
(Run freq.)
A
Run
command
5 sec
Set
Description
value
0
Unit: 0.01 sec.
1
Unit: 0.1 sec.
2
Unit: 1 sec.
Set
value
-
-
1
30Hz
(Target freq.)
(Delta freq.)
10Hz
B
C
5
7
12
5 sec
9-11
9. Basic functions
Min/Max
Factory
range
defaults
0/6000
5.0
0/6000
10.0
0/1
0
Time
[sec]
SV-iC5
Unit
sec
sec