9. Basic functions
9.2

Multi-Step frequency setting

Group
LED Display
Drive
0.0
group
Frq
St1
St2
St3
I/O group
I22
I23
I24
I30
I31
I32
I33
Select a terminal to give Multi-step frequency command among P1-P5 terminals.
If terminals P3-P5 are selected for this setting, set I22-I24 to 5-7 to give Multi-step frequency command.
Multi-step frequency 0 is settable using Frq – [Frequency mode] and 0.0 – [Frequency command].
Multi-step frequency 1-3 are set at St1-St3 in Drive group, while Step frequency 4-7 are set at I30-I33 in I/O
group.
Step
FX or RX
freq
0
1
2
3
4
5
6
7
Parameter Name
[Frequency command]
[Frq mode]
[Multi-Step frequency 1]
[Multi-Step frequency 2]
[Multi-Step frequency 3]
[Multi-function
input
terminal P3 define]
[Multi-function
input
terminal P4 define]
[Multi-function
input
terminal P5 define]
[Multi-Step frequency 4]
[Multi-Step frequency 5]
[Multi-Step frequency 6]
[Multi-Step frequency 7]
P5
P4
P3
-
-
-
-
-
-
-
-
-
-
-
-
Set
Min/Max
Value
Range
5.0
0/400
0
-
0/400
-
-
5
6
7
-
-
0/400
-
-
Step 1
Step 0
Frequency
P3
P4
P5
FX
RX
9-6
Factory
Defaults
0.0
0/8
0
10.0
20.0
30.0
2
0/24
3
4
30.0
25.0
20.0
15.0
Step 2
Step 3
Step 4
Step 5
SV-iC5
Unit
Hz
-
Hz
-
-
-
Hz
Step 0
Step 7
Step 6

Hide quick links: