LG SV-iC5 Series Instruction Manual page 41

Lg inverter instructions manual
Hide thumbs Also See for SV-iC5 Series:
Table of Contents

Advertisement

Frequency setting via potentiometer & operating via the Run key
1
-. Apply AC input power to the inverter.
2
-. When 0.0 is displayed, press the Up ( ) key three times.
-. drv is displayed. Operating method is selectable.
3
-. Press the Prog/Ent ( ) key.
-. Check the present operating method ("1" is run via control terminal)
4
-. Press the Prog/Ent ( ) key and then Down ( ) key once.
5
-. After setting "0", press the Prog/Ent ( ) key.
-. "drv" is displayed after "0" is blinking. Operation method is set via the Run key on the keypad.
6
-. Press the Up ( ) key once.
-. Different frequency setting method is selectable in this code.
7
-. Press the Prog/Ent ( ) key.
-. Check the present frequency setting method ("0" is run via keypad).
8
-. Press the Up ( ) key twice.
9
-. After checking "2" (frequency setting via potentiometer), press the Prog/Ent ( ) key.
-. "Frq" is displayed after "2" is blinking. Frequency setting is set via the potentiometer on the
10
keypad.
-. Turn the potentiometer to set to 10.0 Hz in either Max or Min direction.
-. Press the Run key on the keypad.
-. FWD lamp begins to blink and accelerating frequency is displayed on the LED.
11
-. When run frequency 10Hz is reached, 10.0 is displayed as shown left.
-. Press the STOP/RST key.
-. FWD lamp begins to blink and decelerating frequency is displayed on the LED.
12
-. When run frequency is reached to 0Hz, FWD lamp is turned off and 10.0 is displayed as shown
left.
L1(R)
220VAC
L2(S)
P
P1
N
G
U
Motor
V
W
RUN
STOP/RST
MIN
MAX
Wiring
6-3
6. Basic operation
10 Hz
Freq.
Run key
STOP/RST key
Operating pattern
SV-iC5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents