9. Basic functions
9.6
Stop mode select
Decel to stop
Group
LED Display
Function
group 1
Set F30 to 0 {Decel to stop}.
The inverter decelerates to 0Hz for the preset time.
DC brake to stop
Group
LED Display
Function
group 1
Set F30 to 1 {DC brake to stop} (See page 10-1 for more).
Free run to stop
Group
LED Display
Function
group 1
Set F30 to 2 {Free run to stop}.
The inverter turns off the output frequency and voltage when the run command is OFF.
Parameter Name
F4
[Stop mode select]
Freq.
Run
command
Parameter Name
F4
[Stop mode select]
Parameter Name
F4
[Stop mode select]
Freq, Voltage
Run
command
Set
Min/Max
Value
Range
0
Decel time
Set
Min/Max
Value
Range
1
Set
Min/Max
Value
Range
2
9-18
Factory
Defaults
0/2
0
Factory
Defaults
0/2
0
Factory
Defaults
0/2
0
SV-iC5
Unit
Unit
Unit