LED
Parameter
display
name
H16
[Skip
frequency high
limit 3]
H17
S-Curve
accel/decel
start side
H18
S-Curve
accel/decel
end side
H19
[Output phase
loss protection
select]
H20
[Power On
Start select]
H21
[Restart after
fault reset]
1) Set H10 to 1 to be displayed.
# H17, 18 is used when F2, F3 is set to 1 S-Curve.
Min/Max
range
1/100 [%]
Set the speed reference value to form a curve
at the start during accel/decel. If it is set higher,
linear zone gets smaller.
1/100 [%]
Set the speed reference value to form a curve
at the end during accel/decel. If it is set higher,
linear zone gets smaller.
0/1
Inverter turns off the output when the
phase of the inverter output (U, V, W) is not
properly connected.
0/1
This parameter is activated when drv is set
to 1 or 2 (Run/Stop via Control terminal).
Motor starts acceleration after AC power
is applied while FX or RX terminal is ON.
0/1
This parameter is active when drv is set to
1 or 2 (Run/Stop via Control terminal).
Motor accelerates after the fault condition
is reset while the FX or RX terminal is ON.
Description
7-9
7. Function list
Function group 2
Factory
Adjustable
defaults
during run
35.0
X
40
X
40
X
0
O
0
O
0
O
SV-iC5
Page
9-13
12-5
9-9