Recommendations On The Ac Power Supply - Inspur NF5180M6 User Manual

Hide thumbs Also See for NF5180M6:
Table of Contents

Advertisement

For an AC-powered server, the voltage fluctuates from -10% of the rated voltage to
+10% of the rated voltage.
For AC-powered power equipment and important buildings, the voltage fluctuates
from -10% of the rated voltage to +10% of the rated voltage.
The AC frequency fluctuates from -3% to 3%. The sinusoidal distortion rate of the
voltage waveform is smaller than or equal to 5%.
The server room should be equipped with a self-supplied electric generator set. The
electric generator set should perform automatic power-on/off, automatic recruitment,
remote communication, remote control, and remote detection, and provide standard
interfaces that comply with communication protocols.
The power cable used for AC/DC power distribution should meet the following
requirements:
The conductor in the neutral wire must have the same cross-sectional area as the
conductor in the live wire.
The power feeder should be selected based on the long-term load. If the cross-
sectional area exceeds 95 mm2, a hard bus cable should be used. If there is a
great difference between the short-term load and the long-term load, cables can
be routed by stage.
AC/DC conducting wires should be flame-retardant and be routed according to the
Code for fire protection design of tall buildings (GB50045).

8.10.3 Recommendations on the AC Power Supply

Recommendations on the AC power supply are as follows:
Use a voltage stabilizer or voltage-regulator to respond to unstable voltages. Use
a voltage-regulator in the following situations:
The server is directly powered by the mains supply, and the power supply
-
voltage exceeds the rated voltage by -10% to +10% or the voltage range
allowed for the server.
The server is not directly powered by the mains supply, and the mains voltage
-
exceeds the rated voltage by -10% to +10% or the AC input voltage range
allowed for the DC power equipment.
To prevent interruption or surge of AC power supply, use the UPS or inverter.
The data center should be equipped with self-supplied generator set in case of
mains failure to ensure proper function of important load and important power
load. All electrical equipment such as IT equipment and refrigeration equipment
shall be considered. Check the start-up shock to ensure that the generator can start
reliably. The generator performance should meet the requirements of Code for
Design of Data Centers (GB50174).