Enabling Goose Client - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 4
HMI500
Step REB500
configuration tool
HMI500
8
Final configuration:
The assignment of
GOOSE data
attributes from
selection list
Unassigned
GOOSE data
attributes to
REB500 input
signals is made
9
Download the
configuration to the
REB500 system
10
Post-configuration:
Transfer of the
updated CID/IID file
(see remark under
item 9) to the system
engineering tool
11
-
4.6.4.3

Enabling GOOSE Client

This section describes the pre-configuration of the GOOSE Client.
The GOOSE Client is enabled if at least one of the REB500 input signals has been configured as
GOOSE input. The radio button GOOSE input is only available for specific REB500 signals. The Assign
button is enabled after the Station configuration file (SCD) has been imported.
48
System
engineering tool
-
-
-
Post-
configuration:
Import of the
updated CID/IID
file
If any further configuration changes affect the IEC 61850 model or IEC 61850
communication, then the information should be transferred by repeating steps 2 through
11.
© 2020 - 2022 Hitachi Energy. All rights reserved
Remark
See
Figure
41.
CCF creator uses the information of the Station configuration
description (SCD) and of the REB500 configuration to create the
configuration of the REB500 GOOSE client Sending IED:
Communication section
GSEC Control
DataSet
This configuration is automatically created during
setfile download and the same time, the CID/IID
file is updated.
Used source IED data attributes are marked.
Prevents removing used GOOSE data attributes from the source
IED.
1MRK 500 132-UUS Rev. B
GUID-D2A41405-8484-45BC-B5E2-82EEE0FD8D9B v2
Distributed busbar protection REB500
Operation manual