Requirements To Goose Input Signals; Disabling Goose Client; Goose Send Support; Applications For Goose Send Support - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 500 132-UUS Rev. B
Table 12:
Menu Items
Unassigned GOOSE
Attribute – ABB Ref
Unassigned GOOSE
Attribute – External
Reference
Selection – GOOSE attribute
filter
4.6.4.7

Requirements to GOOSE input signals

Example: The breaker failure protection remote trip (timer t1) and the intertripping to all bay units of a bus
zone (timer t2) implies that the fault still persists at the end of the respective timer. Consequently, the
GOOSE input signal (trip from line protection) mapped to the BFP start signal must therefore be reliably
present during both time steps.
4.6.4.8

Disabling GOOSE client

The GOOSE client is disabled if none of the REB500 input signals have been configured as GOOSE
input and GOOSE data attributes have been deleted in the Configuration/SCS Configuration /IEC
61850-8-1 options.
4.6.5

GOOSE send support

The REB500 can be configured to send information by GOOSE to other IEDs connected to station bus
via central unit interface X1001 (PRP LineA) and X1002 (PRP LineB) respectively.
4.6.5.1

Applications for GOOSE send support

Optocoupler input status (Configuration of events)
The bay unit optocoupler inputs can be assigned to send their status by GOOSE. The necessary
assignment for the binary inputs those concerned is done under Configuration /Binary Module /
Inputs /Details /OC event configuration .
Trip information
The information of predefined tripping signals (see section Combined tripping commands in the
Technical Manual) can be sent by GOOSE.
Figure 43
IED receives the trip information by GOOSE.
Distributed busbar protection REB500
Operation manual
Selection elements
Description
REB500 Internal designation for the bay or central unit.
Full name of the GOOSE data attribute. The full name comprises:
IED name, Logical Device Instance, Prefix, Logical Node Class, logical
Node instance, Data Object name and Data attribute Name
Regular expression which limits the number of GOOSE data attribute in
the list of Unassigned GOOSE attributes:
? = any character
* = none, one or any number of characters
The comparison is case insensitive.
examples: "*_1*Op*", "*_?P*Op*", "*_?P*Op.phs*"
The REB500 GOOSE input signals have to comply with the requirements for the
corresponding standard input signal. Non-conformance may lead into unwanted
operation of the protection system.
illustrates a busbar fault and the resulting information (trip signal) flow assumed that the control
© 2020 - 2022 Hitachi Energy. All rights reserved
Section 4
HMI500
GUID-6F4C3DF2-FE37-46A4-A52E-A7089221BC8F v1
GUID-97F63380-BBD8-486A-B818-ACB387C8B8C1 v1
GUID-578C2619-4034-4EDD-B004-64A8BAE6C09A v2
GUID-B04DB984-1BDC-421A-9967-CDBA00CB0510 v1