Disturbance Recorder; Analogue Inputs - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 4
HMI500
LED. All other (undefined) combinations of the binary input signals (0 0 or 1 1) are indicated by a
yellow LED.
The Status LED on LMI dialog box is saved by clicking OK. The dialog box LMI LED configuration is
active again and a print of the LED labels can be started by clicking Print Labels now. Before initiating a
print job, the Print Range as well as the Label Orientation shall be adjusted.
4.6.8

Disturbance recorder

4.6.8.1

Analogue inputs

Bay Units
The currents measured by the four analogue inputs are always recorded. The five voltage inputs may
only be recorded providing they have been licensed and engineered (optional).
The recording time is doubled if the voltage channels are not activated.
Central Unit
The differential and restraint currents and in addition the phase angle difference (hereinafter referred to
as phase difference) of the currents are recorded per phase (L1..L3, L0) and bus zone. In the event that
several bus zones are interconnected to (L1..L3, L0) and bus zone. In the event that several bus zones
are interconnected to one protection zone, each bus zone shows the same measurement values.
The phase difference is only recorded, if it is enabled in the Recording tab of the CU disturbance
recorder configuration (see
The following diagram is an example of a phase difference record where no BBP trip occurred (since
phase difference value is constantly above the trip range).
IEC19000205 V1 EN-US
Figure 51:
For more information about the phase comparison algorithm, see REB500 Application manual, section
Phase comparison.
62
Figure
53).
Example of a phase difference record
© 2020 - 2022 Hitachi Energy. All rights reserved
1MRK 500 132-UUS Rev. B
GUID-52536CF9-C75C-4743-9600-61A9BB006CDB v1
GUID-D0B26102-1E94-464F-9470-10AB6C2DF107 v2
GUID-35E8BBBC-4498-436E-B89E-83CD577E67CF v3
18000080-IEC19000205-1-en.vsdx