Goose Function Blocks - ABB RELION 620 Series Technical Manual

Protection and control
Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 H
3.14.4.4
Signals
Table 68: RESTVTR Input signals
Name
Uo
Table 69: RESTVTR Output signals
Name
ALARM
WARNING
3.14.4.5
Settings
Table 70: RESTVTR Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
Amplitude Corr
0.9000...1.1000
Angle correction
-20.0000...20.0000
3.14.4.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
3.15

GOOSE function blocks

GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data
types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850 engineering
guide for details.
620 series
Technical Manual
Type
INT32-UL0
Type
BOOLEAN
BOOLEAN
Unit
Step
kV
0.001
V
1
0.0001
deg
0.0001
Default
Description
0
IEC61850-9-2 residual
voltage
Description
Alarm
Warning
Default
11.547
100
1.0000
0.0000
Basic functions
Description
Primary voltage
Secondary voltage
Amplitude correc-
tion
Angle correction
factor
139