ABB RELION REB500 Operation Manual page 107

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 500 132-UUS Rev. B
Table 25:
Alarm
Version check
failed
License check
failed
Repetitive BBP
blocked
Repetitive BFP
blocked
Repetitive Diff
Current Alarm
Repetitive Invalid
BU Currents
Repetitive Output
Relays blocked
Repetitive BU
restarts
Repetitive CU
restarts
CIM HW Failure
CPC HW Failure
BU HW Failure
Missing BIO HW
Module
Missing TRM HW
Module
Missing PIO HW
Module
Wrong TRM HW
Module
IP address
conflict
1) Only once during start-up or normal running state
2) Only once during start-up
Table 26:
Alarm
Permanently
Blocked
Distributed busbar protection REB500
Operation manual
Start-up and repetitive error causes
Event
Major_Error 013
Major_Error 014
Major_Error 016
Major_Error 017
Major_Error 018
Major_Error 019
Major_Error 020
Major_Error 021
Major_Error 022
Major_Error 023
Major_Error 024
Major_Error 025
Major_Error 028
Major_Error 029
Major_Error 030
Major_Error 031
Major_Error 075
Permanently blocked state
Event
Major_Error 176
© 2020 - 2022 Hitachi Energy. All rights reserved
Detection
Description
setting
2)
In case the target version does not match the version of
once
the CU CIM target, the target blocks permanently.
2)
In case the license check during start-up failed (that is
once
some features are activated that are not licensed on this
target), the target blocks permanently.
30 per 600 sec
If a Repetitive BBP blocked alarm is activated, the
target blocks permanently.
30 per 600 sec
If a Repetitive BFP blocked alarm is activated, the
target blocks permanently.
60 per 3,600
If a Repetitive Diff Current Alarm is activated, the
sec
target blocks permanently.
30 per 60 sec
If a Repetitive Invalid BU Currents alarm is activated,
the target blocks permanently.
30 per 600 sec
If a Repetitive Output Relays blocked alarm is
activated, the target blocks permanently.
3 per 600 sec
In case of Repetitive BU restarts, the target blocks
permanently.
3 per 600 sec
In case of Repetitive CU restarts, the target blocks
permanently.
If the diagnosis detects any HW related failure, the CIM
1)
once
blocks permanently .
1)
If the diagnosis detects any HW related failure, the CPC
once
blocks permanently.
1)
If the diagnosis detects any HW related failure, the BU
once
blocks permanently.
2)
If the configured/required BIO HW module is missing, the
once
target blocks permanently.
If the required TRM HW module is missing, the target
2)
once
blocks permanently.
If the configured/required PIO HW module is missing, the
2)
once
target blocks permanently.
2)
If the configured and physical assembled TRM HW
once
module do not match, the target blocks permanently.
2)
If an IP address configuration problem occurs (The main
once
reason is that two interfaces are configured with the
same IP address), the target blocks permanently.
Detection
Description
setting
-
If the error handling detects start-up or repetitive error
causes (see
set.
Table
14), the permanently blocked state is
Section 7
Troubleshooting
101