1MRK 500 132-UUS Rev. B
Trigger operation
Recording commences when at least one of the triggering conditions is fulfilled. The trigger then remains
disabled until the record has been completed and is then enabled again. You must therefore set the
recording period such that all the signals you want to record can be recorded.
IEC18000544 V1 EN-US
Figure 52:
Distributed busbar protection REB500
Operation manual
The trigger inputs are scanned every 16 ms. A trigger signal must have a pulse duration
of at least 16 ms to be certain that it will be detected.
Disturbance recorder – Configuration (Bay Unit)
© 2020 - 2022 Hitachi Energy. All rights reserved
GUID-5C0ABD53-F314-4D93-8387-87EC7FDB40CA v2
13000012-IEC18000544-1-en.vsdx
Section 4