4.6.5.3

Defining signals for GOOSE send

This section describes the configuration of the GOOSE output mapping which is done in HMI500 menu
in Configuration/Binary Module/Outputs/Details.
Distributed busbar protection REB500
Operation manual
Configuration / SCS Configuration – IEC 61850-8-1 options / GCB configuration
GCB configuration Menu Items
Description
Unambiguously identification of the GCB within the
scope of the LLN0. Defined by the System.
Attribute that allows a user to assign an
identification for the GOOSE message.
Unique Identifier of GOOSE messages according
to IEC 61850-8-1 Appendix C.
MAC address to which the GOOSE message is to
be sent. The address shall be an Ethernet address
that has the multicast bit set TRUE.
Range of values from 0 to 4095 according to IEEE
802.1Q.
Range of values 0 to 7 according to IEEE 802.1Q.
As defined in IEC 61850-6 the sending delay on a
data change between the first immediate sending
of the change and the first repetition in ms.
As defined in IEC 61850-6 the source supervision
time in ms (supervision heartbeat cycle time).
Insert a new item at the end of the list.
Deletes the selected item
Only signals which are mapped to a GOOSE control block are sent in GOOSE
messages.
© 2020 - 2022 Hitachi Energy. All rights reserved
18000081-IEC19000203-1-en.vsdx
IEC 61850 identification
GoCBName
GoID (Ed 2)
appID (Ed1)
APPID
DstAddress.Addr
DstAddress.VID
DstAddress.PRIORITY
MinTime
MaxTime
GUID-E887B7F0-A4A2-4864-A005-90A47D83DC53 v3
Section 4
HMI500
Default
0
0
4
4
10000
57