Section 4
HMI500
Only specific Signals can be assigned to GOOSE in HMI500. In the Details Tab of the Binary Module/
Outputs the menu item GOOSE control block assignment is only shown for these specific signals.
IEC19000213 V1 EN-US
Figure 46:
58
For all mapped signals the name of the GCB Name is listed in the GOOSE column in the
Overview tab of the Binary module/ Outputs dialog box.
The combined tripping signals are less flexible than the tripping logic of
the Trip relays output assignment in the Details Tab of Configuration /
Binary Module — Outputs.
If a phase selective function trips that is 23315_BFP TRIP L1
(PTRC.phsA on GOOSE) then also system internally the 23315_BFP
TRIP L1 is set. As a consequence for GOOSE the PTRC. general is
always TRUE on a trip. This in parallel with the phase specific PTRC.phsx
(x = A,B,C,neut) on GOOSE.
The Capability in the service section of the REB500 CID/IID file indicate
that DataSet editing (ConfDataSet), GSEControl editing (GSESettings)
and ReportControl editing (ReportSettings) is allowed by the system
engineering tool. Such changes by the System engineering tool only
takes effect if the SCD File is imported to the HMI500 in (Subst. Config file
in "Configuration /SCS Configuration/IEC 61850-8-1 options /Import
GOOSE data attributes") dialog (see Step 7 in
However, added or modified 61850 communication settings in the
imported SCD file like DataSet, ReportControl and GSEControl are not
reflected in the HMI500 menus.
Configuration / Binary module - Outputs - Details – BU
© 2020 - 2022 Hitachi Energy. All rights reserved
1MRK 500 132-UUS Rev. B
Table
10).
18000078-IEC19000213-1-en.vsdx
Distributed busbar protection REB500
Operation manual