Delete Signal; Caption; Mode - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 500 132-UUS Rev. B
IEC18000511 V1 EN-US
Figure 50:
4.6.7.2

Delete signal

The assignment of a signal is cancelled by marking it in the dialog box and clicking on Delete signal.
4.6.7.3

Caption

The name in the Caption column proposed by the program can be edited by selecting it with the mouse.
A caption can have a maximum of 20 characters.
4.6.7.4

Mode

The user can determine the response of the LED by clicking in the Mode column. The following modes
are possible:
Status: The current status of the signal is displayed.
Latching: The status of a LED is stored until one of the following occurs:
Switch closed green: For a defined ON or OFF state of a switch (breaker / disconnector binary input
signals 0 1 or 1 0) the closed position is indicated by a green LED and the open position by a red
LED. All other (undefined) combinations of the binary input signals (0 0 or 1 1) are indicated by a
yellow LED.
Switch open green: For a defined ON or OFF state of a switch (breaker / disconnector binary input
signals 0 1 or 1 0) the closed position is indicated by a red LED and the open position by a green
Distributed busbar protection REB500
Operation manual
In case of breaker and disconnector position signals only one position signal can be
assigned.
The caption, mode, color and active state configuration can be set once for each LED.
New signal (list of available signals)
A bay protection function picks up
A station protection function trips
It is reset via the local HMI
It is reset by HMI500
It is reset by a binary signal