1MRK 500 132-UUS Rev. B
IEC19000212 V1 EN-US
Figure 72:
Distributed busbar protection REB500
Operation manual
LHMI Test Trip active
When the Test Trip state changes from OFF to ON , the tripping command
21120_EXT_TEST_TRIP is activated and depending on the binary output configuration
see Tripping Command
Section 4.6.3.6
breaker.
The Test Trip state can be toggled as many times as possible as long as the menu will
not be left.
If the Test Trip menu will be left, the Test Trip state changes back to OFF if no
combination with an external test trip input exists. In combination with the external Test
Trip input it might remain in the ON state (if state of input signal 11115_Ext_Test_TRIP is
set to ON).
Leaving the Test Trip menu will require a re-logon to authenticate the user every time.
The Test Trip menu will be left automatically after the configured display timeout, which
can be changed in the LHMI menu Display settings/LHMI/Display Timeout.
© 2020 - 2022 Hitachi Energy. All rights reserved
IEC19000212-IEC19000212-1-en.vsdx
a trip command is sent to the respective circuit