Section 3
System overview
The digital busbar protection REB500 is divided into several hardware units. Bay units measure the line
and bus-tie breaker currents and may be installed close to the respective CTs. They communicate with
the central unit via a process bus. The central unit processes the current signals measured by the bay
units and distributes the tripping signals back to the bay units in the event of an internal busbar fault. The
system can be controlled by a local HMI (LHMI) on the Central unit and Bay units, by comprehensive
external HMI software, or a remote HMI over a station bus connection. Communication with the station
automation system (SAS) is possible via the central unit.
10
When configuring the IP-address for the LHMI Ethernet port to the fixed value of
192.168.0.1, a DHCP server functionality will be activated on this port. A maximum of 10
IP addresses will be assigned automatically, when connected. This functionality is
available on the LHMI port only. Information on how to configure different IP-addresses
can be found in
Section
4.9.5.2.
© 2020 - 2022 Hitachi Energy. All rights reserved
1MRK 500 132-UUS Rev. B
Distributed busbar protection REB500
Operation manual