Distributed busbar protection REB500
Operation manual
GOOSE engineering process
System
engineering tool
-
REB500
System must
be configured
System name
must be
defined
GOOSE client
must be
enabled
-
-
The REB500 ICD
file is imported
The data flow
engineering is
made in the
System
engineering tool
Export of the
Station
configuration
description (SCD
file) and transfer
to the HMI500
-
© 2020 - 2022 Hitachi Energy. All rights reserved
Remark
Enabling GOOSE Client (see
See
Figure 37
and
Figure 38
In addition to the ICD file that describes the IED functions, the
project-specific configuration file is also exported:
Edition 1: CID file (.cid)
Edition 2: IID file (.iid)
Selection of the Edition
Configuration/Communication/SCS Configuration/IEC 61850-8-1
options/Edition x (see
Figure
This Export SCS data process is used initially and after a
configuration change.
Each time the export is started, the original values
of REB500 setting parameters are implemented.
The IED name of the REB500 in the System engineering tool must
match the System name in the REB500 configuration tool.
-
Containing GOOSE data set, report control block, source IED and
destination IED
Configuration/Communication/SCS Configuration/IEC 61850-8-1
options/Import GOOSE data attributes button (see
Figure
36)
39)
Figure
Section 4
HMI500
39).