Figure 3-44 Securing the chassis to the rack
Step 10 Reinstall the power units, bypass unit, MDU (with its support), and UPS font
panels.
After you insert the power unit and bypass unit, rotate the ready switches to
locked state
Step 11 (Recommended) Install a lock for the maintenance bypass switch, as shown in
Figure
----End

3.2.3 (Optional) Installing Antiseismic Kits

Step 1 Determine the positions for installing antiseismic kits based on the marking-off
template.
Step 2 Drill holes for installing expansion bolts, and install expansion bolts.
Step 3 Move the UPS to the installation position over its castors.
Step 4 Remove the lower front panel of the UPS and PDU cover.
Step 5 Secure two antiseismic kits to the front and rear of the chassis using eight M6
screws and four M12 screws.
Issue 13 (2022-01-19)
NO TICE
.
3-30.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
72