Huawei UPS5000-A-30 User Manual page 124

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Item
Outp. freq.
Output
voltage
Freq. track
rate
Bypass Settings
Figure 4-17 Bypass Settings Screen
Issue 13 (2022-01-19)
Description
Specifies the system output
frequency level.
The specific voltage range
depends on the output
voltage level.
This parameter can be
adjusted based on site
requirements. If Output freq.
track rate (Hz/s) is slow, the
inverter frequency is different
from the bypass frequency
when the bypass frequency
changes. If output is
overloaded or the inverter is
faulty, an interruption (less
than 20 ms) occurs when the
UPS transfers from normal
mode to bypass mode. If
Output freq. track rate
(Hz/s) is fast, the inverter
frequency is unstable.
NO TE
Output voltage and Freq. track rateare displayed in the scroll manner. The full display is
as follows:
● Output voltage: 220.0 V (209.0–231.0), Output voltage: 230.0 V (218.5–241.5), Output
voltage: 240.0 V (228.0–252.0)
● Freq. track rate: 0.6 Hz/s (0.1–2.0)
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
50 Hz
50 Hz, 60 Hz
The default
380 V: 209.0–
value is 220.0,
231.0
230.0, and
400 V: 218.5–
240.0 when
241.5
the voltage
415 V: 228.0–
level is 380 V,
252.0
400 V, and 415
V respectively.
0.6 Hz/s
0.1 Hz/s to 2.0
Hz/s
114