Huawei UPS5000-A-30 User Manual page 128

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Issue 13 (2022-01-19)
Item
Description
Cell float
Indicates the battery float
volt.
charging voltage. The
parameter is configurable
in any mode.
Flt. volt.
Option to correct the float
comp.
voltage based on the
battery temperature when
a battery temperature
sensor is connected. The
value is configurable in any
mode.
Temp. comp.
Coefficient for correcting
coef.
the float voltage based on
the battery temperature
when a battery
temperature sensor is
connected.
Temp. comp.
Basic point of temperature
center
compensation.
Discharge
Figure 4-22 Discharge screen
Item
Description
Max. dis.
Indicates the maximum
time
battery discharge time.
When the discharge time
reaches the value, the UPS
powers off.
Shallow Discharge Test
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default
Value Range
Value
2.25 V/cell
2.23 V/cell–
2.30 V/cell
Enabled
Disabled,
Enabled
3.3 mV/
0.0 mV/
°C*cell
°C*cell–6.0
mV/°C*cell
25 °C
20–30
Default
Value Range
Value
24h
0h–48h
118