UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Rack-mounting the UPS
Step 1 Remove the left and right side panels, handles, and MDU from the UPS chassis, as
shown in
connected to the chassis.
Figure 3-18 Removing the left and right side panels, handles, and MDU from the
UPS chassis
1.
2.
3.
4.
Step 2 Place the ready switches on the power unit and bypass unit into the unlocked
state
Two persons are required to move a power unit. During movement, keep the
power unit and bypass unit always in a horizontal direction.
Issue 13 (2022-01-19)
Figure
3-18. Before you remove the MDU, remove the cables that are
Remove the rubber plug from the chassis.
Remove the left and right side panels.
Remove the handle.
Remove the MDU.
NO TE
Before you remove the side panels, unscrew the mounting ear of the power unit.
, and remove the power unit and bypass unit, as shown in
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Figure
3-19.
55