Communications Settings; Control - Huawei UPS5000-A-30 User Manual

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Item
Single batt.
dis. voltage
deviation
alarm thres.
(%)
Batt.
charging
capacity
mismatch
Bat mode
shut
Backup
time
warning
Remain.
cap.
warning

4.3.2.2 Communications Settings

Figure 4-32 Comm. Config. page

4.3.2.3 Control

You can control the system running status on the Control page.
Issue 13 (2022-01-19)
Description
The calculation formula is (Charge/
Discharge voltage – Average voltage)/
Average voltage x 100%.
After this function is enabled, an alarm
is generated if the configured battery
capacity exceeds the charging capacity
of the rack.
In battery mode, the UPS can
automatically power off according to
the preset shutdown delay time. If the
parameter is disabled, this function is
not available.
An alarm is generated if this parameter
is set to Enable and the backup time is
less than the warning threshold.
An alarm is generated if this parameter
is set to Enable and the remaining
capacity is less than the warning
threshold.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default
Value
Value
Range
20
10–30
Disable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
133