5.10 Clearing the EPO State

Procedure
Step 1 Turn off the external EPO switch that connects to the dry contact. Ensure that the
EPO switch is not in the EPO state.
Step 2 Clear the EPO alarms in the system.
Issue 13 (2022-01-19)
LCD
On the main screen, choose Alarms > Clear Faults. After the dialog box is
displayed, press
and the EPO alarm can be cleared, as shown in
5-22
and
Figure
5-23.
Figure 5-22 Alarms screen
Figure 5-23 Clearing the alarm