UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Figure 5-20 EPO alarm on the LCD
Figure 5-21 EPO alarm on the WebUI
----End
5.10 Clearing the EPO State
Procedure
Step 1 Turn off the external EPO switch that connects to the dry contact. Ensure that the
EPO switch is not in the EPO state.
Step 2 Clear the EPO alarms in the system.
●
Issue 13 (2022-01-19)
LCD
On the main screen, choose Alarms > Clear Faults. After the dialog box is
displayed, press
and the EPO alarm can be cleared, as shown in
5-22
and
Figure
5-23.
Figure 5-22 Alarms screen
Figure 5-23 Clearing the alarm
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Figure
167